IMPORTANT
|
|
|
November 5, 1998
To all users of this repair kit:
We have very recently discovered that manual reset only versions of the McDonnell & Miller 150S and 157S, the versions with snap switches, may not operate correctly throughout their operating temperature range.
In order to avoid the chance of any field failures, which could lead to fire, we will replace or provide means to repair these products. This kit is meant to facilitate the repair of certain variations of these products.
Federal law requires that you must promptly take all action necessary to insure repair or replacement of the control.
Again, this applies only to the manual reset versions. The standard versions of the 150S and 157S are unaffected, and can be sold and used with confidence. All products with a date code of September 1998 (98J) or later, are also unaffected, and can be used with confidence.
The products to be inspected and repaired are listed below:
| 172104 | 150S-B-M | 173302 | 150S-M-MD-HD | 177006 | 157S-RL-M | ||
| 172702 | 150S-M | 173802 | 157S-A-M | 177306 | 157S-R-M | ||
| 172802 | 150S-M-MD | 175402 | 157S-M | 178502 | 158S-M | ||
| 172901 | 150S-M-J | 175412 | 157S-M-MD | 178702 | 158S-M-HD | ||
| 173203 | 150S-M-HD | 176551 | 157S-RB-M | 310463 | SWA-150S-M |
Date codes of products to be inspected and repaired be are listed below:
| 96J | September 1996 | 97E | May 1997 | 98A | January 1998 | ||
| 96K | October 1996 | 97F | June 1997 | 98B | February 1998 | ||
| 96L | November 1996 | 97G | July 1997 | 98C | March 1998 | ||
| 96M | December 1996 | 97H | August 1997 | 98D | April 1998 | ||
| 97A | January 1997 | 97J | September 1997 | 98E | May 1998 | ||
| 97B | February 1997 | 97K | October 1997 | 98F | June 1998 | ||
| 97C | March 1997 | 97L | November 1997 | 98G | July 1998 | ||
| 97D | April 1997 | 97M | December 1997 | 98H | August 1998 |
A) S Series manual reset units
built between September of 1996 and August of 1997
· These units cannot be repaired in the field.
· These units can be easily identified by the white
reset button on the side of the switch housing.
· Install a current head unit, either a 150S-M-HD
or 150S-M-MD-HD, as appropriate.
· We will replace those units at no charge. Contact
your local wholesaler for details.
· Also, you should be prepared to return the old
heads. Again, contact your local wholesaler for details.
B) S Series manual reset units
built between September of 1997 and August of 1998
· These units can be easily identified by the large
red reset button on the bottom of the switch
housing.
· These units should be field repaired using the enclosed
kit.
· Additional field repair kits and instructions
are available for immediate shipment, at no charge,
from your local wholesaler, from our location here in Chicago,
or from our local representative in your area.
· It is important that you help us keep track of
where each repair kit is used. The enclosed reply
card should be returned to us once a repair is complete.
C) Reasonable actual costs for field labor associated with either head replacement or field repair will be reimbursed. In order to be reimbursed, we must have received the reply card or the replaced head. For details, please call Steve Mueller, our Customer Service Manager, at (773)-267-1600.
We realize that this action may be seen as an extreme inconvenience, particularly as we enter the heating season. However, we believe it prudent to promptly act to insure that product in the field can be relied upon to perform safely. We apologize for any inconvenience this will cause.
Very truly yours,
John Cecilia
Marketing Manager